Overview
VIBROCONTROL 1500
VC1500EN / C103845.002 / V 09 / 14.04.2015
- 7 -
The standard equipment contains:
o
Two (2) relays with potential-free switch-over contacts for signaling event
messages. The relays are assigned to the set limit values.
o
One (1) OK relay with potential-free switch-over contacts for monitoring
of the power supply, the functions of the microprocessor system and the
connected sensors.
o
Two (2) analogue outputs proportional to the casing vibration.
o
CAN-Bus interface for data transmission between the VIBROCONTROL
1500 and a super-ordinate computer.
All setting up tasks are carried out directly at the instrument by entry or
selection of parameter values. Setting up is also possible using the
VIBROCONTROL 1500 Control-Center-Software
.
The connections for the power supply, measurement sensors, analogue and
contact outputs as well as the CAN-Bus interface are made through plug-in
terminal blocks.
2.2
Possible measurement and monitoring tasks
2.2.1 Display values
Corresponding to the national and international prescription for evaluation of
machine vibrations, the effective (RMS) value of vibration velocity is used for
display and monitoring.
Display value
Abbreviation
Unit
Vibration velocity
v
mm/s
in/s
There is also the possibility to display and monitor the value of rolling-
element bearing condition; unit of rolling-element bearing condition: BC
(Bearing Condition)
Rolling-element bearing
condition
BC value
BC
dimensionless
Measurement and monitoring of temperature is possible by connecting
PT-100 sensors.
Temperature
T
°C °F