Operating the VIBROCONTROL 1500
VIBROCONTROL 1500
VC1500EN / C103845.002 / V 09 / 14.04.2015
- 31 -
7.5
Limit value violation - Display
If the pushbutton
is again pushed the instrument displays information
about the last limit value violation by the measured value which has taken
place.
If the measured value has not violated the limit values
L1v
,
L2v
,
L1temp
,
L2temp
,
L1BC
,
L2BC
the following information is displayed.
Fig.15: Display of limit value violation; in this
case no limits have been violated
If any of the limit values
L1v
,
L2v
,
L1temp
,
L2temp
,
L1BC
or
L2BC
have
been violated the display indicates the last violation with the associated
channel description.
Fig.16: Display of limit value violation; L1v in channel violated
If the
ESC
button is pushed while this is being displayed the current
information about the limit value violation is deleted from the display. Only the
next arbitrary violation of a limit value leads to a new display of a limit value
violation.
Note:
By pushing the
ESC
button the self-latching relay LIM2 is not reset.
This only occurs with the help of terminals 25 and 26 or a new restart of the
VIBROCONTROL 1500 instrument.
Pushing the
button again leads to a return to the base display.
Note:
When the reset channel is closed, the display does not show the state
of the LIMs correctly. In this case only the LEDs indicates the correct
state of the LIM channels.
7.6
Menu-guided instrument dialogue
By pushing the button
ENTER/MENU
the menu programme of the
instrument is called and displayed.
With the buttons
and
one can page backward and forward through the
individual points of the menus.
To return to the previous display, push the
ESC
button.