VIBROCONTROL 1500
Operating the VIBROCONTROL 1500
- 48 -
VC1500EN / C103845.002 / V 09 / 14.04.2015
Channel setup – (SENS)
Here the sensitivity (transmission factor) settings for both sensors are carried
out. The entry of sensor-specific date is carried out separately for each
channel. The display for selecting the setups is reached through the display
"Channel setup" und "Select channel". The desired channel A or B is
selected and confirmed with
ENTER.
With the help of buttons
and
the option
SENS
is selected in the Setup
menu and confirmed with
ENTER
.
Fig. 47: Selection of the settings
You are then required to enter a password. The password for the sensor-
specific setting is
1500
. The individual password numbers are entered one
after the other with the help of the buttons
and
and each number is
confirmed with the button
ENTER
after it is entered.
Fig. 48: Password entry
After entry of the correct password the display for setting the sensor
sensitivity appears. Using the buttons
and
select between 100 mV/g or
OFF and confirm with
ENTER
.
With the help of the button
ESC
it is possible to exit the menu without having
carried out a change to the setting.
On selection of 100 mV/g the VIBROCONTROL 1500 assumes that the
sensor being connected has a transmission factor of 100 mV/g. In order to
consider a deviating transmission factor, the instrument can be adjusted by a
Trim
factor to the actual transmission factor of the sensor to be used. The
calibration of the VIBROCONTROL 1500 to the sensor that will be used then
takes place with the help of the Trim factor, which can be set within the range
of 0.50 to 1.99.