Installation
VIBROCONTROL 1500
VC1500EN / C103845.002 / V 09 / 14.04.2015
- 17 -
Mounting in an AC-211x protective housing
The AC-211x protective housing offers mechanical protection as well as
protection against weather influences. Up to two VIBROCONTROL 1500
instruments plus an AC-4111 power supply can be mounted in the protective
housing.
Note:
Due to the limited air circulation there is a reduction in the permissible
operating temperature range:
1 x VIBROCONTROL 1500 + 1 x AC-4111: 0 °C …+45 °C
2 x VIBROCONTROL 1500 + 2 x AC-4111: 0 °C … +40 °C
Do not install any other components into the protective housing!
Note:
The connections between the VIBROCONTROL 1500 unit and the power
supply
AC-4111
is already established.
Remove the
VIBROCONTROL 1500 unit from the DIN Rail before mounting or
connecting other parts.
•
Disconnect all Phoenix plugs in the lower terminal strip.
•
Pull the black lever under Port LIM 1 and remove the
VIBROCONTROL 1500 unit from the DIN rail.
•
Disconnect all Phoenix plugs in the upper terminal strip.
•
Connect the new wiring and lay the cable screens carefully at the cable
glands.
How to mount the VIBROCONTROL 1500 unit into the protective
housing.
•
Connect all upper Phoenix plugs at the VIBROCONTROL 1500 unit.
•
Mount the VIBROCONTROL 1500 unit onto the DIN rail.
•
Mount all lower Phoenix plugs at the VIBROCONTROL 1500 unit. Use a
screwdriver to do this carefully.
Fig.2: VIBROCONTROL 1500 unit mounted on a DIN trail
1. Upper terminal strip
2. DIN rail
3. Lower terminal strip