Section 1 Introduction
Installation and Operation Manual
X-PR-SLA5840-Series-RevB-RT-eng
Part Number: 541B201AAG
October, 2017
Table 1-4 SLA58XX Series Certifications
Mark Agency
Certification
Applicable
Standard Details
UL
(Recogonized)
Class I, Div 2, Group A, B, C, D
Class I, Zone 2, IIC T4
Class II, Zone 22
UL & CSA
Standards
E73889 Vol 3, Sec 4
ATEX
II 3 G Ex nA IIC T4 Gc
EN60079-0:2012
EN 60079-15:2010
KEMA 04ATEX 1118X
IECEx
II 3 G Ex nA IIC T4 Gc
IEC 60079-0:2011
IEC 60079-15:2010
IECEx DEK 14.0072X
KOSHA
Ex nA IIC T4
15-AV4BO-0641
15-AV4BO-0640
CE
EMC Directive 2014/30/EU
Directive 2011/65/EU
EN:61326-1:2013 EMC
RoHS
*ATEX/IECEx Special Conditions for safe use:
1. The module shall be installed in a suitable enclosure providing a degree of protection of
at least IP54 according to EN 60529 / IEC 60529, taking into account the environmental
conditions under which the equipment will be used.
2. When the temperature under rated condition exceeds 70 °C at the cable or conduit entry
point, or 80 °C at the branching point of the conductors, the temperature specification of
the selected cable shall be in compliance with the actual measured temperature values.
3. Provisions shall be made to prevent the rated voltage from being exceeded by transient
disturbances of more than 40%.
4. The equipment shall only be used in an area of not more than pollution degree 2, as
defined in IEC 60664-1.