Fsetpoint
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Float
RW
0…3.4E+38
206
33/3
0xA119…0xA11A/ 41241…41242
Floating point variant of
Setpoint
.
Fsetpoint
shows the setpoint in the capacity unit for which the instrument is set. Like
Fmeasure
,
Fsetpoint
is dependent of
Capacity
,
Capacity 0%
,
Capacity Unit
and
Sensor Type
.
Setpoint Slope
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
RW
0…30000
10
1/2
0x0022/35
The value of this parameter represents the time it would take to adjust the setpoint if it were changed from 0 to 100%. This
feature can be used to smooth 'nervous' controller behavior, e.g. to reduce setpoint overshoot or undershoot.
The supported range corresponds to 0…3000 seconds. Default value = 0.
Example:
If
Setpoint Slope
= 100 it will take 10 seconds to adjust the setpoint if it is changed from 0 to 100%. A setpoint change of 20%
will take (20%/100%)*10 seconds = 2 seconds.
Analog Input
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
R
0…65535
11
1/3
0x0023/36
This parameter contains a digital translation of the analog input signal (if applicable).
Valve Output
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned long
RW
0…
16777215
55
114/1
0xF208…0xF209/61961…61962
Controller output signal for driving the control valve, where 0…16777215 corresponds to 0…100%.
Sensor type
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
RW
0…255
22
1/14
0x8170/33127
The following sensor types are supported:
Instrument type
Value
Description
Controller
1
Liquid volume
2
Liquid /gas mass
3
Gas volume
Sensor
129
Liquid volume
130
Liquid/gas mass
131
Gas volume