Classic Terrazzo
®
Corner Washfountain with Air Valve Control
WF2613
Installation Instructions
Bradley Corporation • 215-1523 Rev. E; EN 06-915B
4
4/6/2007
RIGHT WALL
LEFT WALL
Std. Ht. Juv. Ht. Std. Ht. Juv. Ht.
11-1/4" to 13-1/4"
9-1/4" to 10-1/4"
6" to 11"
6" to 8-1/2"
286mm to 337mm
235mm to 260mm
152mm to 279mm
152mm to 216mm
12"
8-1/4"
12"
8-1/4"
305mm
210mm
305mm
210mm
DIM.
A
B
Rough-In Specifications
Use this range of heights
when hook-up is made with
a coupling and nipple (2"
drain through wall must not
interfere with diagonal
frame member on pedestal).
Rough-In Notes:
1. All pipes and fittings not furnished by Bradley are shown in broken lines.
2. Supply lines for one to two washfountains should be 1"; for three washfountains 1-1/4"; for more than three washfountains, pipe sizes
should be increased proportionately.
3. Overhead supplies must be reduced to 1/2" copper tube to pass through support tube.
4. Check valve inlets are 1/2" NPT.
5. Dimensions shown in parentheses are millimeters.
Type A
Off-line vent with supplies from below.
Type O
Off-line vent with supplies from above.
54” (1372)
WASHFOUNTAIN
TOP VIEW
SIDE VIEW
SIDE VIEW
TOP VIEW
COLD
HOT
TRAP
54” (1372)
WASHFOUNTAIN
BOWL
HOT
COLD
TRAP
2” NPT DRAIN THRU FLOOR
(OPTIONAL) STUB UP 3” (76)
ABOVE FLOOR
1” NPT SUPPLIES THRU
FLOOR (STUB UP 2-1/2” (64)
ABOVE FLOOR)
CENTER OF
WASHFOUNTAIN
10”
(254)
10”
(254)
18-1/2”
(470)
10”
(254)
8-1/2”
(216)
9-3/4”
(248)
9-3/4”
(248)
12-3/4”
(324)
7-1/4”
(184)
A
B
7-1/4”
(184)
18-1/2”
(470)
12-3/4”
(324)
8-3/8”
(213)
8-3/8”
(213)
10”
(254)
A
TRAP FOR
WALL
OUTLET ONLY
DRAIN THRU
FLOOR
TRAP LOCATED
BELOW FLOOR
4”
(102)
DRAIN
THRU WALL
SUPPLIES
THRU
WALL
TRAP FOR WALL
OUTLET ONLY
DRAIN
TRHU WALL
SUPPLIES AND DRAIN THRU FLOOR,
TRAP LOCATED BELOW FLOOR.
1” NPT SUPPLIES FROM ABOVE
MUST REDUCE TO 1/2” NOM.
COPPER TUB ON THESE
CENTERS TO PASS THRU WASH
FOUNTAIN
4”
(102)
2” NPT
DRAIN
THRU WALL
(STUB OUT
TO
SUIT TRAP
DIMENSION)
(OPTIONAL)
1” NPT
SUPPLIES
THRU WALL
(OPTIONAL)
4-1/2”
(114)
CLEARANCE HOLE
CENTER OF
WASHFOUNTAIN
2” NPT DRAIN THRU FLOOR
(OPTIONAL) STUB UP 3” (76)
ABOVE FLOOR
2” NPT DRAIN
THRU WALL
(STUB OUT TO
SUIT TRAP
DIMENSION)
(OPTIONAL)
CLEARANCE HOLE
RIGHT WALL
LEFT WALL
FLOOR
LEFT WALL
RIGHT WALL
LEFT WALL
FLOOR
NOTE:
UPC AND IPC RESTRICT THE VERTICAL
DISTANCE FROM THE FIXTURE OUTLET TO THE TRAP
WEIR TO NOT MORE THAN 24". CHECK STATE AND
LOCAL CODES FOR VARIANCES.