Operation with Residual-Current-Operated Circuit-Breaker
The frequency converters FCS01 have been sized for operation with a 30 mA
residual-current-operated circuit-breaker sensitive to universal current.
If several FCS01 frequency converters are operated at a residual-current-op‐
erated circuit-breaker, the leakage currents must be reduced against PE.
Operation in IT Mains
General Information
Via jumpers at the top and bottom of the device, the FCS01 frequency con‐
verters can be set for operation at IT mains and for reduction of leakage cur‐
rents.
At the Top of the Device (Mains Input)
Fig.5-6:
Mains Input Jumper in Position "2"
Setting
Position
Effect
0
Operation at the IT mains
1
No effect
2
Standard position (condition as supplied)
Fig.5-7:
Jumper Position at the Top
DOK-INDRV*-FCS01******-IT01-EN-P
Rexroth IndraDrive Fc Drive Controllers Frequency Converters FCS01
Bosch Rexroth AG
39/69
Instructions for Use