A
Terminal side
B
Actuator side
Fig.8-11:
Connection of actuators, for signal cables > 10 m
8.3.7
Connecting Lines to Tension Spring Connection Points
General Information
Connect the lines for peripherals and voltage supply to the tension spring con‐
nection points both at the IndraControl L45/L65/L85 and to the Rexroth Inline
terminals.
Use unshielded lines for the digital inputs and outputs and the voltage supply.
Use shielded lines to connect the analog inputs and outputs.
Lines with a connection cross-section ranging from 0.2 mm
2
to 1.5 mm
2
(AWG
24 – 16) can be connected. These lines permit the supply of signals of up to
250 V AC/DC and 5 A.
Connecting Unshielded Lines
Fig.8-12:
Connecting lines to tension spring connectors
Bosch Rexroth AG
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
62/81
Installation and Maintenance