top-hat rail all the way to the left side of the IndraControl L45/L65/L85, until a
secure connection via the PCI
PLUS
bus is established.
Mounting the end clamp
Finally, attach end clamps to both sides of the Rexroth Inline station. These end
clamps ensure that the station is securely mounted to the top-hat rail and are
also provided as lateral termination elements. These termination elements are
included in the scope of delivery of the IndraControl L45/L65/L85.
8.1.3
Dismounting the IndraControl L45/L65/L85
Disconnecting additional modules
from IndraControl L45/L65/L85
To dismount the IndraControl L45/L65/L85, first disconnect the function mod‐
ules mounted to the left of the IndraControl L45/L65/L85 from the latter. First
remove the left-hand end clamp (CLIPFIX) and slide the function modules along
the top-hat rail to the left until the plug connection of the PCI
PLUS
bus is sepa‐
rated.
Removing the first Rexroth Inline
terminal
Thereafter, remove the first Rexroth Inline terminal that is mounted to the right
of the IndraControl L45/L65/L85. Proceed as follows:
●
Remove the labeling field, if present.
If any of the terminal is provided with more connectors than one, all
these connectors are to be removed from the terminal.
●
Pry out the connector of the terminal to be removed by pressing on the
rear connector shaft latch.
●
Remove the connector(s).
●
Remove the power connector from the IndraControl L45/L65/L85. This
ensures that the feathers of the voltage jumpers and the keyway/feather
key connection are prevented from damage. Moreover, the terminal can
be accessed more easily.
●
Actuate the release mechanism (1 in the following figure) and remove the
terminal perpendicularly to the top-hat rail (2 in the following figure).
Fig.8-1:
The first Rexroth Inline terminal is to be removed before the IndraCon‐
trol L45/L65/L85 is dismounted.
Removing the IndraControl L45/
L65/L85 from the top-hat rail
Now the IndraControl L45/L65/L85 can be removed from the top-hat rail by
loosening the fixing claw on the bottom side by means of a tool (screwdriver)
and pulling the IndraControl L45/L65/L85 off the top-hat rail from below, tilting
it and removing it upwards.
Bosch Rexroth AG
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
50/81
Installation and Maintenance