Sensor supply
From U
S
via a PTC fuse
Output voltage
Typ. Uext. – 1V
Nominal current (total)
0.2 A
Short-circuit protection, overcurrent pro‐
tection
Typ. 0.6 A
Criteria to connect 2-wire proximity
switches:
Quiescent current
Voltage drop
< 2.5 mA
< 6 V
Fig.7-13:
Data of the digital inputs
The input terminals are provided with LEDs displaying the respective state of
the inputs.
LED 1, 2, 3, 4
Meaning
Off
The assigned input is not set.
Yellow
The assigned input is set.
Fig.7-14:
Status LEDs of digital inputs
An additional two-color LED (identified by D) emits green light in case the 24 V
voltage is present and red light in case of a short-circuit or overload.
LED D
Meaning
Off
24 V voltage is missing.
Green
24 V voltage is present.
Red
Short-circuit or overload
Fig.7-15:
LED D
7.3.3
Digital Outputs
Two terminal strips with a total of 8 digital outputs are arranged between the
digital inputs and the terminals for the voltage supply.
Bosch Rexroth AG
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
40/81
Connections and Interfaces