LED
Status
L (link)
On: Link to network is available
Off: No connection to network
S (send)
On: Data packets are sent.
Off: No data is sent
7.4.2
Ethernet Interface (optional)
X7E3, X7E4 Ethernet network con‐
nection
Connectors X7E3 and X7E4 can be used to connect the IndraControl L45/L65/
L85 to an Ethernet network.
The connection requirements defined for 100BaseTX in IEEE 802.3 are appli‐
cable.
RJ45, female connector, 8-pin
Type
Ethernet 100Base TX
Cable length
100 m max.
Cable type
CAT5e with S/STP
Transmission rate
10 or 100 MBit/s
max. 100 m
1
8
2
1
3
4
5
6
7
8
Ethernet RJ45
Ethernet
to the network
Fig.7-21:
Ethernet interface
Bosch Rexroth recommends the use of a STP cable of category 5.
According to the configuration in the application software, these connections
can be used for another TCP/IP network or for an RT Ethernet network.
The two plugs correspond to a twofold switch in a TCP/IP network.
LED
Status
L (link)
On: Link to network is available
Off: No connection to network
S (send)
On: Data packets are sent.
Off: No data is sent
7.4.3
PROFIBUS DP (optional)
X7P PROFIBUS DP interface
Optionally, the IndraControl L45/L65/L85 provides a PROFIBUS interface ac‐
cording to DIN EN 50170, part 2.
D-Sub female connector, 9-pin
Type
RS485
Bosch Rexroth AG
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
44/81
Connections and Interfaces