Voltage
The voltage of the UPS is DC 24 V.
Current carrying capacity
The performance of the buffer depends on the buffer period.
Currently, the voltage supply is not used and does therefore not
need to be connected!
Controls with a production index < 201 have the the contacts 2.1
and 2.2 changed!
The production index is the three-digit number after the parts num‐
ber (see Type Plate).
The LED "U
M
" lights green if the wiring is correct.
7.2.2
Internally Generated Voltages
+7.5 V Inline Supply U
L
The +7.5-V Inline supply voltage is generated from the supply voltage U
LS
inside
the IndraControl L45/L65/L85 and is supplied through all connected Rexroth
Inline I/O terminals. It is the logic voltage supply (via voltage jumpers) of the
Rexroth Inline terminals.
This logic circuit starts at the IndraControl L45/L65/L85 and is supplied through
all terminals of a station.
Function
Logic voltage is supplied from the Inline supply to all terminals of the station.
Voltage
The voltage in this circuit is 7.5 V.
Generation of the Inline supply
The Inline supply is generated from the supply voltage U
LS
of the IndraCon‐
trol L45/L65/L85.
Current carrying capacity
The maximum current carrying capacity of the Inline supply is 2 A.
+24 V Analog Supply (U
ANA
)
The 24-V analog supply is also generated from the voltage U
LS
. It starts in the
IndraControl L45/L65/L85 and is supplied through all Rexroth Inline I/O termi‐
nals. It is the voltage supply (via voltage jumpers) U
ANA
of the Rexroth Inline
analog terminals.
Function
The peripheral equipment of the terminals for analog signals is supplied from
the analog circuit.
Voltage
The voltage in this circuit is 24 V.
Provision
The analog voltage U
ANA
is generated from the IndraControl L45/L65/L85 from
the logic voltage U
LS
Current carrying capacity
The current carrying capacity of U
ANA
is max. 0.5 A.
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
Bosch Rexroth AG
37/81
Connections and Interfaces