RE 92076-01-B/2021-04-22, Bosch Rexroth AG
Troubleshooting |
A4... with HS5E(V)(L) control system Series 1x and 30 99
/104
Table 28: Malfunction table of HS5E control systems
Malfunction
Possible cause
Remedy
Pressure statically at approx
5...12 bar, cannot be changed
Supply voltage not within the permissible range
Diagnosis: Check the status LEDs
Check, whether the central connector XH4
is connected to the HS5E pilot control valve
Check voltage at the last interconnection
point (terminal strip) upstream the HS5E
pilot control valve
Command value for pressure, swivel angle or
power (optional) is 0 bar or 0%, respectively
If you use, for example, exclusively closed-
loop pressure control, provide a swivel angle
command value of 100%
Swivel angle sensor defective
Check swivel angle measurement,
see chapter 8.1.5.4 on page 73
Piston is stuck in the HS5E pilot control valve
Contact Rexroth Service
Pressure too low
Actual pressure value acquisition incorrectly
configured
Check actual pressure value in IndraWorks
and, if required, correct configuration of
actual pressure value acquisition
Replace pressure transducer, see page 89
Change installation location of the pressure
transducer (do not install upstream of
the preload valve; if possible, close to the
consumer)
Pressure transducer defective/not connected
Diagnosis: Measure signal from PT and compare
with indication on the pressure gauge
Replace pressure transducer, see page 89
Connect pressure transducer
Control system does not work in closed-loop
pressure control
Increase swivel angle command value
Check that the hydraulic system is leak-free
and that the withdrawal is not excessively
high
HS5E pilot control valve faulty
Replace the HS5E pilot control valve,
see chapter 10.5.1 on page 87
Pressure too high
Actual pressure value acquisition incorrectly
configured
Check actual pressure value in IndraWorks
and, if required, correct configuration of
actual pressure value acquisition
Replace pressure transducer, see page 61
Pressure transducer defective/not connected
Diagnosis: Measure signal from PT and compare
with indication on the pressure gauge
Replace pressure transducer, see page 61
Connect pressure transducer
HS5E pilot control valve faulty
Replace the HS5E pilot control valve,
see chapter 10.5.1 on page 87
Insufficient flow
Pressure controller active
Increase pressure command value
Actual swivel angle acquisition improperly set
Recalibrate swivel angle sensor
Rotational speed speed too low (slip, incorrect
frequency, wrong motor)
Contact machine or system manufacturer
Damage to the pump (excessive pump leakage)
Rotary group damaged,
Contact Rexroth Service
Wear/mechanical damage to the control system Replace the control system, contact Rexroth
Service