RE 92076-01-B/2021-04-22, Bosch Rexroth AG
Installation |
A4... with HS5E(V)(L) control system Series 1x and 30 61
/104
7.6.8 Selection, installation location, and installation direction of the pressure
transducer
To reduce the number of variants, only the 630 bar pressure stage of the HS5E
control systems is listed. If necessary, it is also possible to combine other pressure
stages (under selection of the appropriate electrical interface!) It is, however, only
possible to deal with orders for pressure transducers of this type separately from
the HS5E(V)(L) control system.
A differentiation is made on a signal-specific basis between
• sensors with a current interface, and
• sensors with a voltage interface.
Here, the usual signal limits are between 0...20 mA or 0...10 V.
Within these limits, there are further modifications that depend, for example, on
whether cable breaks are to be monitored too.
From a technical point of view, the efficiency of the pressure transducer must be
matched to the HS5E(V)(L) control system to make it possible to achieve optimum
results for accuracy, dynamics, and reproducibility.
The pressure transducers that we recommend are listed in the RE sheets of the
respective HS5E system.
The pressure transducer "HM20-2X" (for version HS5E(V)(L)P) with (4...20 mA)
current interface has a two-wire connection and makes it possible to transfer signals
on a noise-immune basis across relatively long distances (depending on the cable
and the permissible ohmic resistance of the pressure transducer).
Looping in of further pick-ups is possible taking into account the respective input
resistances.
For more detailed information about the pressure transducer, see data sheet 30272.
The pressure transducer "HM20-2X" with (0.1...10 V) voltage interface has a three-
wire connection and a built-in DC/DC converter that effectively rules out interference
with the analog signal that is caused by the voltage supply.
You should avoid a transmission of the signal across long distances.
The benefit of the pressure transducer is that you easily check the signals using
a voltmeter without needing to interfere with the connection lines.
For more detailed information about the pressure transducer, see data sheet 30272.
The pressure transducer is connected to ports
X2M1
and
X2M2
. Alternatively, it can
also be connected to the HS5E pilot control valve via the central connector. In case
of connection of the pressure transducer via the central connector, the supply
voltage must comply with the specification.
Selection of the pressure
transducers
Pressure transducer
HM20-2x (current)
Pressure transducer
HM20-2x (voltage)
Pressure transducer
connection