RE 92076-01-B/2021-04-22, Bosch Rexroth AG
Installation |
A4... with HS5E(V)(L) control system Series 1x and 30 57
/104
7.5 Performing flushing cycle
In order to remove foreign particles from the system, Bosch Rexroth recommends
a flushing cycle for the hydraulic system before the first commissioning. To avoid
internal contamination, do not include the axial piston unit in the flushing cycle.
Use an additional flushing unit to perform the flushing cycle. Follow the
instructions of the flushing unit's manufacturer for the exact procedure during the
flushing cycle.
7.6 Electrically connecting the HS5E(V)(L) control system
The machine or system manufacturer is responsible for the layout of the electric
control.
For electrically controlled HS5E(V)(L) control systems, the electric control must be
connected correctly according to the circuit diagram of the system manufacturer.
Damage to the device due to incorrect installation is not covered by the warranty!
1.
Switch off the power supply to the relevant system component.
2.
Connect the HS5E pilot control valve electrically (24 V).
7.6.1 Cable sets
Accessories for HS5E(V)(L)
Material number
Data sheet
Plug-in connector, 12-pin for central connection XH4
without cable (assembly kit)
R900884671
08006
Plug-in connector, 12-pin for central connection XH4
with cable set 2 x 5 m
R900032356
Plug-in connector, 12-pin for central connection XH4
with cable set 2 x 20 m
R900860399
Pressure transducer HM 20-2X,
Measuring range 630 bar (4 ... 20 mA)
R901342035
30272
Test device VT-PDFE-1-1X/V0/0
R900757051
29689-B
Compact power supply unit VT-NE32-1X
R900080049
29929
An Ethernet M12 to RJ45 connection cable (ports X7E1 &
X7E2), additional information in type designation RKB0044/
xxx.x (xxx.x: length in meters)
R911172135
7.6.2 Wiring the electronic components
In general, the following applies:
– Keep the number of intermediate terminals as low as possible.
– You are not allowed to align electromagnetic sources of interference in the
immediate vicinity of the HS5E pilot control valve.
– You are not allowed to route power cables in the vicinity of the HS5E pilot
control valve.