7 Gate Setting Configuration
7.1 Selecting the Gate Mode of Operation
Insert the programming key, select “SYSTEM SETUP”, select “CONTROL MODE” and
select “GATE”. The screen to the left will appear.
If the Hopper Gate is equipped with a “Location Detection Sensor”, select “READ
BACK”, if not select “OFF”.
Using the navigation buttons, move the cursor to the desired option and press the
Enter button. The screen will return to the previous screen.
7.2 Calibrating the Gate “Read Back” Sensor
Insert the programming key, select “SENSORS AND VALVES”, and select “GATE
SETUP”. The screen to the left will appear.
Setting the MIN calibration:
1.
Close the Hopper gate to its minimum opening.
2.
Measure this opening of the gate (see note on next page)
(see note on next page)
(see note on next page)
(see note on next page).
3.
Using the navigation buttons, move the cursor to the “00-Min” option and press
the Enter button.
4.
Use the Right or Left navigation button to move the cursor under the number to
be changed.
5.
Using the Up or Down navigation buttons change the setting to match the gate
opening.
6.
Note: the Volts reading will change to reflect the actual reading from the sensor.
7.
Once the numbers have been changed to match the gate opening, press the
Enter button.
Setting the MAX calibration:
1.
Open the Hopper Gate to its maximum opening.
2.
Measure this opening (see note on next page
(see note on next page
(see note on next page
(see note on next page).
).
).
).
3.
Using the navigation buttons, move the cursor to the “10 Max” option and press
the Enter button.
4.
Use the Right or Left navigation button to move the cursor under the number to
be changed.
5.
Using the Up or Down navigation buttons change the setting to match the gate
opening.
6.
Note: the Volts reading will change to reflect the actual reading from the sensor.
7.
Once the numbers have been changed to match the gate opening, press the
Enter button.