System settings (Service menu – Settings)
Logamatic EMS – 6 720 801 387 (2011/05)
34
6
What is the desired
maximum flow
temperature?
25 °C to 60 °C
45 °C
2)
For how many days
should maximum flow
temp. be maintained?
0 days to 20 days
4 days
2)
Every how many days
should the flow temp.
be reduced?
Direct normal
operat., every day,
every 2nd day to
every 5th day
Every day
2)
By how many K should
the flow temperature
be reduced
respectively?
0 K to 20 K
5 K
Adjustment only if, for flow
temperature reduction,“direct
normal operation” has not been
selected.
4)
Do you wish to change
the switching program?
Yes, No
no
When selecting “yes” the system
jumps to the heating circuit
switching program.
Should the switching
programme be
optimised?
Yes, No
no
Start and stop times are
automatically adjusted according to
the outside temperature, room
temperature and building type (heat
storage capacity).
What reduction mode
should be used for
holiday?
Outdoor
compensation
mode,
reduced mode,
room compensation
mode, switch-off
mode
Outdoor
setback
mode
See page 37.
Setting for “room compensation
mode” only if a remote programmer
(e.g. RC2x) has been allocated to
the heating mode. If “reduced
mode” is selected, the normal night
temperature is used.
What outside temp.
should be used?
-20 °C to +10 °C
5 °C
Temperature threshold for outdoor
setback mode (
Æ
page 37).
Adjustment only if setback mode for
holiday was set to “outdoor setback
mode.”
1) Depending on the boiler the setting range can be limited
2) Not possible or not available with boilers with UBA1.x or DBA.
Menu item
Input range
Standard
setting
Other information
Table 14 Navigator for service menu of SETTING\HEATING CIRCUIT 1