System settings (Service menu – Settings)
Logamatic EMS – 6 720 801 387 (2011/05)
28
6
Example:
Fig. 6
This greatly simplified example shows how the adjusted outside temperature follows the
outside temperature, but does not reach its extreme values.
1
Current outside temperature
2
Adjusted outside temperature
6.1.2 Minimum outside temperature
The minimum outside temperature is the average value of each of the coldest outside temperatures
or recent years, and it has an influence on the heating curve. The value can be taken from the heat
demand calculation which should be done for every building, or from the climatic zone chart for your
region.
In the basic setting any changes in the outside temperature have an effect after a delay
of three hours at the latest (30 x 6 minutes = 180 minutes) on the calculation of the
outside temperature compensated control.
B
To control the calculated, adjusted outside temperature and the actual measured
outside temperature: open the menu for
Diagnostics\monitor value 4
boiler\burner.
6 720 618 477-05.1RS
2
1