System settings (Service menu – Settings)
6
Fig. 7
Setting of the heating curve. Left: setting the gradient by means of design temperature
and minimum outside temperature. Right: parallel offset possible by means of offset or
set room temperature.
T
minA
Minimum outside temperature
T
A
Design temperature (flow temperature that should be achieved at min. outside temperature)
1
Setting: design temperature 75 °C, minimum outside temperature – 10 °C (standard curve)
2
Setting: design temperature 75 °C, minimum outside temperature – 20 °C
3
Setting: design temperature 50 °C, minimum outside temperature – 10 °C
4
Setting: minimum flow temperature 35 °C
5
Setting: design temperature 75 °C, minimum outside temperature – 10 °C (standard curve)
6
Parallel offset of standard curve by changing the 3 or by increasing the set room temperature
7
Parallel offset of the standard curve by changing the offset – 3 or by reducing the set room temperature
6.4.4 Reduction modes (night reduction)
There are a number of different setback modes available, which allow night setback to be adjusted
to suit the differing needs of the user:
•
Reduced operation
: the rooms are maintained at a reasonable temperature at night by constant
heating operation (pump runs constantly). A set room temperature for nighttime can be set. It is
at least 1 K lower than the set day temperature. The heating curve is calculated in accordance
with these details.
We recommend these settings for an underfloor heating system.
•
Shutdown operation
: boiler and heating circuit pump are off, frost protection is active. The
pump only starts in frost protection mode.
This setting is not recommended if there is a risk that the building would cool down too severely.
T minA
T
A
T
A
T minA