System settings (Service menu – Settings)
Logamatic EMS – 6 720 801 387 (2011/05)
26
6
6
System settings (Service menu – Settings)
B
Press
+
+
simultaneously, to open the
SERVICE MENU
.
B
Turn the
rotary selector to the left until
settings
is selected.
B
Press
to open menu
SERVICE\SETTINGS
.
6.1
System data
B
Press
button to select
plant data
.
The menu
SETTINGS\SYSTEM
opens.
Note that the menu items shown will vary depending on the heating system.
Menu item
Input
range
Standard
setting
Other information
Have you installed a module for
the low loss header?
Yes, No
No
In association with MCM10 the
setting is automatically set to “Yes”;
screen is hidden.
1)2)
Is a sensor for a low loss header
connected?
No,
at the
boiler, at
the low loss
header
module
No
If a low loss header module is used,
connect the temperature sensor to
the low loss header module.
3)
4)
Is heating circuit 1 installed
(unmixed heating circuit)?
Yes, No
Yes
How many mixed heating circuits
are installed?
0 to 3
0
Setting the address on the rotary
coding selector of the mixer module
(basic setting HK2).
1)
Have you installed a solar
module?
Yes, No
No
1)
Table 10 Navigator for service menu SETTINGS\SYSTEM
SERVICE MENU
quick operation
settings
diagnosis
servicing
B
SERVICE\SETTINGS
B
plant data
boiler data
domestic hot water
heating circuit 1