Logamatic EMS – 6 720 801 387 (2011/05)
33
System settings (Service menu – Settings)
6
What outside temp.
should be used for
reduced operation?
– 20 °C to +10 °C 5 °C
Temperature threshold for outdoor
setback mode (
Æ
page 37).
Adjustment only if the setback mode
is set to “outdoor setback mode”.
Frost prot.
What temp. should be
used to trigger frost
protection?
Outside
temperature, room
temperature, no
frost protection
Outside
temperatur
e
Room temperature adjustment only
if RC2x or RC35 have been
assigned to the heating circuit
(
Æ
page 38).
Which frost protection
temp. should be used?
-20 °C to +10 °C
5 °C
Refers to outside temperature
(
Æ
page 38).
From which outside
temperature should the
reduction be
interrupted?
OFF,
-30 °C to +10 °C
OFF
Reduction in accordance with
DIN 12831 (
Æ
page 39).
Should domestic hot
water priority be
activated?
Yes, No
no
Mixer
2)
Is a mixer installed?
Yes, No
Yes
Can only be set for heating circuit 2
onwards.
2)
What running time
does the mixer have?
10 s to 600 s
120 sec.
2)
What increase should
be used for the boiler?
0 K to 20 K
5 K
2)
Screed drying
2)
Should a drying cycle
be carried out?
Yes, No
no
Adjustment only if floor has been
selected. DHW heating is not
enabled while screed is drying.
2)
Every how many days
should the flow temp.
be raised?
Every day, every
2nd day to
every 5th day
Every day
2)
By how many Kelvin
should the flow
temperature be
increased in each
case?
0 K to 40 K
5 K
2)
Menu item
Input range
Standard
setting
Other information
Table 14 Navigator for service menu of SETTING\HEATING CIRCUIT 1