Logamatic EMS – 6 720 801 387 (2011/05)
47
Diagnosis
7
7.1
Function test
With this menu you can trigger specific individual EMS components, in order to test their function.
1), 2), 3)
The available functions and the possible settings vary depending on the system installed.
B
Hold the button
pressed down and simultaneously turn the rotary
selector to change the setting:
e.g.
BURNER OFF
to
BURNER
ON
.
The change takes effect when you release the button
.
B
Turn the rotary selector
to switch between different displays
(function test).
1) This function is only possible to a limited extent with boilers with UBA-H3.
2) This function is not possible or not available with boilers with UBA1.x or DBA.
3) This function is only possible to a limited extent if a HM10 hybrid module is used.
Observe the information which appears on the display when you switch to menus or
enter settings. Press any button or turn the rotary selector to confirm the information.
No settings will be allowed that might result in damage to the components. This is why
some settings may not be accepted.
valve 1 cl. 2 cl.
FCT. TEST\BOILER
ignition OFF
flame OFF
flame current 0.0
μ
A
B
BURNER ON
act. boil. tmp. 60°C
FCT. TEST\BOILER
air temperature 32°C
flue gas temp. 78°C
flame OFF
B
BURNER OFF