76
en | Appendices
MAP 5000
2019-09 | 25 | F.01U.168.332
Installation manual
Bosch Security Systems B.V.
4
Select the type of entry point for all entry route points.
Entry Point Type
Behavior
Delay 'Normal'
Door point that starts the entry delay with the value 'Normal'
Delay 'Extended'
Door point that starts the entry delay with the value 'Extended'
Follower
Point that does not trip an alarm as long as the entry delay is
running
Tab.
8.4:
Entry Point Types
Programming delayed reporting for all intrusion points of the area
1.
For all points of the point type
Intrusion
and
Intrusion 24h
, set the parameter
Supports
Delayed Reporting
to
Yes
.
2.
For reporting
(Event Manager > Panel Event Groups > Properties > Reportable Events)
,
set a
Transmission Delay
that is the same as the exit delay (typically 45 sec. / at least 30
sec.) for
External Intrusion Alarm
.
8.2.5
Arming with automatic bypass
Points that are not in normal state and therefore prevent arming can be automatically
bypassed for arming. These points are automatically unbypassed again when the system is
next disarmed.
1.
Program point to point type
Intrusion (Bypassable)
or
Intrusion 24h (Bypassable)
.
2.
Set the maximum number of points that can be bypassed on arming under
MAP5000 >
Maximum Bypass Count per Area
(typically 1 - value range is not specified by the
standard).
3.
Set the maximum number of times that a point can be bypassed on arming under
MAP5000 > Maximum Times A Device Can Be Bypassed
(typically 1 - value range is not
specified by the standard).
4.
Set the permission
May Bypass Detectors In Area
for the user:
User Manager >
Permission Sets > Arm Category
.
8.2.6
Automatic arming / disarming
The control center is located in the secured area.
1.
Include a new area if not yet present.
2.
Include a control center if not yet present.
3.
Include the area in the scope of the control center:
Local Area
.
Programming two outputs for signaling the armed / disarmed state
1.
Connect one free output in each case with the device
LED
.
2.
Using the wizard, program one output with the behavior item
Area Armed
and a second
output with the behavior item
Area Disarmed
.
3.
The signal must be time-limited. Enter a corresponding time (typically 10 sec. / maximum
of 30 seconds) for
Activation Duration
.
Automatic arming at a predefined time: defining the arming time
1.
Start the schedule wizard and define the time of arming.
2.
As action, select
Arm Area(s) Using Exit Delay
.