8.1.7
Connection of an LSN fire detector as a technical detector
!
Warning!
Configuration
The configuration of an LSN fire detector may not impact the arming function.
This means that arming needs to be possible even with a tripped detector.
!
Warning!
Retroactive effects
By connecting an LSN fire detector, no negative retroactive effects on the intrusion
functionality may happen.
Notice!
Mechanical removal lock
The LSN fire detector bases have a mechanical removal lock function which can be activated
or deactivated. With activating the mechanical removal lock, removing the detector without a
mechanical tool is not possible.
For a VdS compliant installation, activate the mechanical removal lock function.
8.2
Requirements in accordance with EN 50131 grade 3
Notice!
If not all requirements in accordance with this standard can be satisfied or only a lower grade
can be met, the compliance mark (EN 50131 grade 3) must be either removed or adapted.
8.2.1
Selecting the default setting
1.
2.
If the panel validation in accordance with EN 50131 grade 3 fails, do
not
proceed with
programming the panel.
8.2.2
Connectable peripherals
To comply with the requirements for proper functioning of the panel (i.e. detection and
forwarding of intrusion, hold-up, tamper and trouble states), only peripherals may be
connected that are certified in accordance with EN 50131 grade 3 or grade 4.
8.2.3
Arming / disarming without entry / exit delay
Arming outside the secured area, e.g. with arming device
1.
Include a new area if not yet present.
2.
Connect a free input with the device key switch.
3.
Using the wizard, select the type
Static
or
Dynamic
, the user and function of the key
switch
Arm / Disarm Area
. Now select the area that is to be armed / disarmed. For exit
delay, select
No Delay
.
4.
Select the area in the properties field of the
Key Switch > Area
.
5.
In the properties field of the
Control Center
, include the area in the scope
Local
Area
or
Additional
Areas in Scope
Programming two outputs for signaling the armed / disarmed state
1.
Connect one free output in each case with the device
LED
.