MAP 5000
Maintenance and service | en
67
Bosch Security Systems B.V.
Installation manual
2019-09 | 25 | F.01U.168.332
The initialization phase, indicated by a blinking LED, starts.
P
The LEDs on the main panel and all other installed modules start indicating and the
system is ready for operation again.
LED status
Description
Off
No function
Fast blinking
Connection setup
Slow blinking
Data exchange
Permanently lit
Operating state
Restoring the initial state of the panel
1.
Put the panel in
Failsafe mode
(see below).
2.
Update the firmware.
Failsafe mode
Forcing failsafe mode
Programming and panel firmware are deleted and RPS passcode is reset to default settings
when executing this option.
1.
Open the tamper switch.
2.
De-energize the main panel (e.g. disconnect the small white connector at the rear of the
panel).
3.
Press and hold the installer button.
4.
Connect voltage (e.g. plug in small white connector again).
5.
Release the installer button after 30 seconds.
6.
Wait until operating LED is permanently lit (can take several minutes).
7.
Transfer panel firmware “MAP_Update.Cumulative …tar.bz2“ again using RPS.
Forcing extended failsafe mode
Programming, panel firmware and history are deleted and network settings are reset (DHCP,
0.0.0.0) when executing this option.
4
Carry out steps 1 – 6 of the above, then carry out steps 2 – 7.