12.5
Underwriters Laboratories (UL)
Household Fire Warning System
–
Install at least one UL Listed four-wire latching type smoke detector rated to operate over
the voltage range of 11.2 VDC to 12.3 VDC. The maximum smoke detector load is 50 mA.
–
Install one UL Listed 85 dB audible device rated to operate over the range of 11.2 VDC to
12.3 VDC as required for this application. Program the bell cut-off time for at least four
minutes. Refer to Programming Item 107 in
Section 5.2.2 System Programming Items
,
page 43.
–
Install end-of-line resistor P/N: 47819 after last smoke detector.
–
Do not use a printer interface module.
–
Where two-wire addressable devices are used, do not place fire and intrusion devices on
the same zone.
–
The system must be able to operate for at least 24 hr, and generate a full alarm output for
at least 4 min without AC power.
Household Burglar Alarm Unit
–
Install at least one UL Listed 85 dB audible device rated to operate over the voltage range
of 11.2 VDC to 12.3 VDC.
–
Install at least one IUI-EZ1 Control Center.
–
Program all zones to use end-of-line supervision.
–
Install intrusion initiating devices rated to operate over the voltage range of 11.2 VDC to
12.3 VDC.
–
Program all intrusion zones for audible notification.
–
Do not exceed 60 sec when programming Exit Delay. Refer to Programming Item 126 in
Section 5.2.2 System Programming Items
, page 43. Do not exceed 45 sec when
programming Entry Delay. Refer to Programming Item 127 in
Section 5.2.2 System
Programming Items
, page 43. Program the bell cut-off time for at least of four minutes.
Refer to Programming Item 108 in
Section 5.2.2 System Programming Items
, page 43.
–
The system must be able to operate for at least 24 hr, and generate a full alarm output for
at least 4 min without AC power.
4.3.3
Fire Alarm
Verification
Required option
Depends on control
panel and sensors
Disabled
Enabled unless
sensors can self-
verify
4.5
Call Waiting Cancel Required option
Depends on user
phone line
Disabled
Enabled if user
has call waiting
1
Programming at installation site might be subordinate to other UL requirements for the intended application.
2
Combined Entry Delay and Abort Window should not exceed 1 minute.
3
If the cross zone timer ends and a second cross zone point is not faulted, the system sends an intrusion alarm unverified report.
Paragraph Number
in ANSI/SIA CP-01
Feature
Requirement
Range
Shipping
Default
Recommended
Programming