24
en | System Installation and Configuration
Easy Series
F01U087835 | 02 | 2008.10
System Reference Guide
Bosch Security Systems, Inc.
Table 2.6
Wireless Device Test Procedures
After each successful point test, the system announces "Point xx was tested."
If you test a point and the system only announces "Point xx," the point number is assigned,
but has not been tested:
–
If you prefer specific point numbers, do not continue. Fix any issue with the device and
re-test until the system announces "Point xx was tested."
–
If you do not prefer specific point numbers, you can test them later through the Installer
Menu. When the system completes the testing, the system announces "Wireless devices
not configured."
7.
The system says, "System test complete.”
2.7.5
Add Users, Tokens, and Key Fobs
1.
From the User Phone Menu (refer to
Section 2.7.2 Initiate a Phone Session from the Control
Panel
, page 22), press [4] to enter the User Menu.
2.
From the User Phone Menu, press [4] to enter the User Menu.
3.
Press [1] to add a new user. After you add a new user, you can also assign a token,
passcode, and key fobs to that user.
4.
Repeat Step 4 to add more users.
5.
Press [#] to return to the User Menu.
Water Sensor/Low-
temperature Sensor
Water Sensor:
Select one of the following methods:
–
Short the water probe pins for at least 5 sec.
–
Submerge the water probe in water for at least 5 sec.
Low-temperature Sensor:
Short the "T" pads for at least 5 sec.
1
To test the inertia detector, create a shock to cause an inertia alarm, and then restore alarm.
2
To test the glass break detector, use a special tool to cause a glass break alarm, and then restore the alarm.
3
If you tamper the detector, the control panel enrolls the detector, but does not test it. You must create the appropriate alarm and
restore the alarm to test the detector.
Device
To Test
i
NOTICE!
If you plan to use a programming key to copy control panel data for back up or use on another
system, back up the data now. Refer to
Section 4.3 Programming Keys
, page 36.