Easy Series
Agency Approvals and Requirements | en
115
Bosch Security Systems, Inc.
System Reference Guide
F01U087835 | 02 | 2008.10
Quick Reference
Refer to the following table for programmable features, shipping defaults, and recommended
programming that comply with the ANSI/SIA CP-01 False Alarm Reduction standard.
The system test button tests all points, all outputs, the control panel, and the communicator.
Refer to
Section 8.1 Test the System
, page 61 for more information.
Paragraph Number
in ANSI/SIA CP-01
Feature
Requirement
Range
Shipping
Default
Recommended
Programming
1
4.2.2.1
Exit Time
Required
(programmable)
For full or auto
arming: 45 sec to
2 min (255 sec max)
60 sec
60 sec
4.2.2.2
Progress
Annunciation/
Disable for Silent
Exit
Allowed
Individual control
centers can be
disabled.
All control
centers
enabled.
All control centers
enabled.
4.2.2.3
Exit Time Restart
Required Option
For re-entry during
Exit Time
Enabled
Enabled
4.2.2.5
Auto Stay Arm on
Unvacated
Premises
Required option
(except for remote
arm)
If no exit after full
arm
Enabled
Enabled
4.2.4.4
Exit Time and
Progress
Annunciation/
Disable for Remote
Arm
Allowed option (for
remote arm)
Can be disabled for
remote arm
Enabled
Enabled
4.2.3.1
Entry Delay(s)
Required
(programmable)
30 sec to 4 min
2
30 sec
At least 30 sec
2
4.2.5.1
Abort Window for
Non-fire Zones
Required option
Can be disabled by
zone or zone type
Enabled
Enabled (all
zones)
4.2.5.1
Abort Window Time
for Non-fire Zones
Required
(programmable)
15 sec to 45 sec
2
30 sec
At least 15 sec
2
4.2.5.1.2
Abort Annunciation Required option
Annunciate that no
alarm was
transmitted
Enabled
Enabled
4.2.5.4.1
Cancel
Annunciation
Required option
Annunciate that a
Cancel was
transmitted
Enabled
Enabled
4.2.6.1 and 4.2.6.2 Duress Feature
Allowed Option
No 1+ derivative of
another user code;
no duplicates of
other user codes
Disabled
Disabled
4.3.1
Cross Zoning
Required Option
Programming
needed
Disabled
Enabled and two
or more zones
programmed
4.3.1
Programmable
Cross Zoning Time
Allowed
Can program
Per
manufacturer
Per walk path in
protected
premises
4.3.2
Swinger Shutdown Required
(programmable)
For all non-fire
zones, shut down at
one or two faults
One fault
One fault
4.3.2
Swinger Shutdown
Disable
Allowed
For non-police
response zones
Enabled
Enabled (all
zones)