ICP-CC488 |
Installation Guide | 16.0
Programmable Outputs
EN
| 70
Bosch Security Systems, Inc. | 12/08 | F01U089457-02
When programming Test Report options, specify the
hour and minute of the day the report is required,
and how often to send the report. Test reports are
reported on a daily basis from every day to every
fifteen days. Refer to
Section 5.1.2 Set the Number of
Days until the First Test Report
to set the first test
report.
If Test Reports are not required, program
the repeat interval in Location 434 as 0.
Program the Test Report Time as 24:00
to send reports every 30 min.
Example
If you want to send Test Reports once every seven
days at 11:35 PM, program Locations 428 to 429 as:
[2 3 3 5 7 1 7]
15.29 Test Reporting Dialer Options
Location
435
0
No report allowed
1
Report to Receiver 1
2
Report to Receiver 2
4
Report to both Receiver 1 and Receiver 2
8
Report to Receiver 2 only if Receiver 1 fails
Location 435 is set by default to report only to
Receiver 1. You can select whether Test Reports are
sent to Receiver 1, Receiver 2, or both, Receiver 2
only when Receiver 1 fails, or no reporting.
16.0 Programmable Outputs
The ICP-CC488 Control Panel has four fully-
programmable outputs on the main printed circuit
board and one programmable output that operates
the codepad buzzer. The four outputs are set by
default to operate as horn speaker, fire alarm
verification, strobe, and internal screamer.
Programmable outputs require four parameters to
operate correctly.
Table 54: Output Parameters
Parameter
Description
Event Type
The Event Type specifies when an output
is activated. The Output Event Types are
listed in
Section 16.2
on page 71 . Enter
the code for the Output Event Type into
the two corresponding locations for the
output.
Polarity
Polarity determines whether the output
operates for the duration of the event,
pulses for the duration, operates only
once (one shot), or latches on. The
Polarity options are listed in
Table 56
on
page
76
.
Time Base/
Time
Multiplier
The Time Base and Time Multiplier
parameters determine how long and how
often the output operates. Refer to
Section 16.4 Output Timing
.
Location
436 to 465
Location
Default
Output 1 (Default – Horn
Speaker)
Event Code
436
1
Event Code
437
14
Polarity
438
0
Time Base
439
0
Time Base Multiplier
440
0
Time Base Multiplier
441
0
Output 2 (Default – Fire Alarm With Verification)
Event Code
442
2
Event Code
443
7
Polarity 444
10
Time Base
445
2
Time Base Multiplier
446
1
Time Base Multiplier
447
5
Strobe Output (Default – Strobe – Reset After 8 hrs.)
Event Code
448
2
Event Code
449
0
Polarity 450
6
Time Base
451
4
Time Base Multiplier
452
0
Time Base Multiplier
453
8
Relay Output (Default – Sirens Running)
Event Code
454
1
Event Code
455
15
Polarity 456
1
Time Base
457
0
Time Base Multiplier
458
0
Time Base Multiplier
459
0
Codepad Buzzer (Default – Entry/Exit Warning and Day
Alarm)
Event Code
460
0
Event Code
461
13
Polarity 462
2
Time Base
463
1
Time Base Multiplier
464
0
Time Base Multiplier
465
1