54
INSTALLER SETTINGS menu settings (for installers only)
6 720 617 763 (2008/09)
8.1.4 INSTALLER SETTINGS: Solar sys parameters
8.1.5 INSTALLER SETTINGS: Fault history
8.1.6 INSTALLER SETTINGS: Cust service address
Solar sys parameters menu
structure
Default set-
ting
Setting range
Personal
setting
Description
starts on page
1. Standard system
–
–
–
SP: ON temperature differ-
ence
8 K
3 K ... 20 K
(not lower than “SP: OFF tempera-
ture difference” +1 K)
K
SP: OFF temperature differ-
ence
4 K
2 K ... 19 K
(not higher than “SP: ON tempera-
ture difference” – 1 K)
K
T2: Max. solar cylinder tem-
perature
60 °C
15 °C ... 90 °C
°C
Maximum collector tempera-
ture
120 °C
100 °C ... 140 °C
°C
SP: Collector grp 1 pump
mode
Auto
Auto | Manual On | Manual Off
PE: Therm disinfect pump mode Auto
Auto | Manual On | Manual Off
Solar optimisation
Collector group 1 area
0.0 m
2
0.0 m
2
... 150.0 m
2
m
2
Collector group 1 type
Flat plate col-
lector
Flat plate collector | Vac tube col-
lector
Climate zone
90
0 ... 255
Optimizing influence DHW
0 K
0 K (= function off) ... 20 K
K
CH circuit optimizing influ-
ence
0.0 K
0.0 K (= function off) ... 5.0 K
K
Run solar system
No
No | Yes
Tab. 16
Fault history menu structure
Default
setting
Setting range
Personal
setting
Description
starts on page
01/01/2008
16:11
Fault EA
(example of last fault)
– –
–
09/25/2008
18:45
FAULT 44 - IPM IDENT. 10
(up to maximum of 19 past faults)
– –
–
Tab. 17
Cust service address menu
structure
Example
Setting range
Personal
setting
Description
starts on page
Telephone number
012345 6789
Max. 20 characters
Name
Heating
installer
Max. 20 characters
Tab. 18