60
INSTALLER SETTINGS menu settings (for installers only)
6 720 617 763 (2008/09)
8.4 Configuring the solar thermal
system
Installer settings: Solar system config
Use this menu if you want to configure the solar
heating system, e.g. at start-up or when changing
the system.
•
Solar sys option E Thermal disinfection
for
thermal disinfection
For menu structure and adjustment ranges
Æ
page 53.
8.5 Parameters for solar thermal
system
Installer settings: Solar sys parameters
The default parameter settings on this menu are
suitable for many common system dimensions.
Use this menu if you want to finely adjust the
parameters to suit the installed solar thermal sys-
tem.
8.5.1 Commissioning the solar thermal system
Installer settings: Solar sys parameters
Before commissioning the solar thermal system
you must:
B
Fill and bleed the solar thermal system.
B
Check the parameters for the solar thermal
system and, if necessary, finely adjust them to
suit the installed system.
PE: Therm disinfect pump mode
: Use this menu
item to select the operating mode of the pump
(PE) for the thermal disinfection process.
–
Auto
: Automatically controlled operation
according to the set parameters.
–
Manual On
: Switches the pump perma-
nently on (e.g. for function test when com-
missioning).
–
Manual Off
: Switches the pump perma-
nently off (e.g. for servicing work on the
pump without having to interrupt heating
operation).
•
Run solar system
: Use this menu option to
commission the solar thermal system.
–
Yes
: Solar thermal system is active. The
ISM control outputs are enabled for auto-
matic control purposes.
–
No
: Solar thermal system is not active. The
ISM control outputs are disabled for auto-
matic control purposes but can be
switched on manually.
For menu structure and adjustment ranges
Æ
page 54.
The heating system’s solar thermal
system has to be configured manu-
ally. Automatic configuration of the
heating system (
Æ
Section 8.2,
page 56) does not configure the
solar system.
An example system configuration is
shown in Section 2.6 on page 11.
Fill and bleed the solar thermal sys-
tem according to its documentation
and prepare it for commissioning as
described this Section.
The designations of the pumps and
the temperature sensors, e.g. (PE)
or (T1), are also used in the ISM in-
stallation instructions.