96
en | Installation of the Pipe System
Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926
Operation Guide
Bosch Sicherheitssysteme GmbH
1
2
3
30°
Positioning the air sampling opening depending on air
speed
1
Aspiration pipe with air
sampling openings
2
Exhaust speed <
0.5
m/s
3
Exhaust speed >
0.5
m/s
6.4.2
Detection in the Bypass
Notice!
For detection in airflows ≥ 2
m/s, additionally feed the exhaust from the FCS-320 back into
the airflow area. Cut the end of the air-return pipe at an angle of 45°.
1
2
3
4
b
1/2 b
Positioning the air-return pipe – example with an air-
conditioning duct (bypass)
1 Air-conditioning duct
2 Duct adapter
3 Aspiration
4 Air-return Pipe
b Width of air-conditioning duct
For details on connecting the air-return pipe, please see
.
For FCS‑320 planning in these applications, see
Planning for Forced Airflow, page 69
See also
–
Planning for Forced Airflow, page 69
–
–