Aspirating Smoke Detector
Installation of the Pipe System | en
101
Bosch Sicherheitssysteme GmbH
Operation Guide
2018.04 | 2.0 | F.01U.130.926
6.9
Detonation Safety Barrier
1
1
4
2
3
3
> 1 m
> 1 m
FA
S-420
ser
ies
1
Detonation Safety Barrier
2
Air-return pipe connection
3
Steel pipe connection
4
Pipe system connection
The detonation safety barriers are integrated into the pipe system and the air return at a
minimum distance of 1
m from the aspirating smoke detector. The detonation safety barrier is
glued to the FCS-320 on the side of the pipe system or the air-return pipe via a transition
screw connection and connected to the side of the unit via a steel pipe. The connection
between detonation safety barrier and steel pipe/transition screw connection is made using a
¾" screw connection.
Notice!
To create a gas-tight connection between the detonation safety barrier and steel pipe/
transition screw connection, a sealing tape or thread seal must be used.
The flow direction for installing the detonation safety barrier is secondary.
6.10
Test Adapter
1
2
FA
S-420
ser
ies
Installing the test adapter in the pipe system
1
Test adapter
2
Pipe system connection
For test purposes, the pipe system connection is simply pulled out and the test pipe
connected directly to the aspirating smoke detector. However, this is not possible if the
aspiration pipe system has to be permanently mounted. A test adapter should be used for this
application.
The test adapter is glued into the pipe system in the direct vicinity of the aspirating smoke
detector. During normal operation, the test adapter must always be closed. It is only opened
for maintenance and service purposes in order to admit test gas or smoke.