Aspirating Smoke Detector
Planning | en
43
Bosch Sicherheitssysteme GmbH
Operation Guide
2018.04 | 2.0 | F.01U.130.926
With detonation safety barrier
Number of air sampling openings
Pipe
shape
U
Fans
1
2
3
4
5
6
7
8
9
10
11
12
…
32
I
6.9
46
46
46
46
38
l [m]
≥9
68
68
68
68
68
68
U
6.9
60
60
60
60
60
60
≥9
60
60
60
60
60
60
60
60
M
6.9
80
80
80
80
80
80
70
70
70
≥9
120 120 120 120 120 120 120 120 120
2 x U
6.9
80
80
80
80
80
80
80
80
≥9
100 100 100 100 100 100 100 100
Results
The following modules can be used with the relevant settings for class B or A:
–
0.015% LT/m (0.05% LT/m) module – with a sensitivity of min. 0.12% LT/m (0.4% LT/m)
–
0.1% LT/m (0.25% LT/m) module – with a sensitivity of min. 0.2% LT/m (0.5% LT/m)
–
0.5% LT/m (0.8% LT/m) module – with setting 0.5% LT/m (0.8% LT/m)
System parameters possible:
–
I-pipe system
9
V fan voltage, max. 80
m total pipe length for U-pipe system
–
U-pipe system
6.9
V fan voltage, max. 110
m total pipe length
9
V fan voltage, max. 110
m total pipe length
–
M-pipe system
6.9
V fan voltage, max. 110
m total pipe length
9
V fan voltage, max. 160
m total pipe length
–
Double U-pipe system
6.9
V fan voltage, max. 140
m total pipe length
9
V fan voltage, max. 160
m total pipe length
Notice!
The sensitivity value is based on measurements with standard test fires (old value in
brackets).
I-pipe system for space protection
The diameters of the air sampling openings should be taken from the relevant table for each
pipe configuration:
1 pipe system
FCS-320-TP1
FCS-320-TT1
2 pipe systems
FCS-320-TP2
FCS-320-TT2
FAS / FCS
A
B
C
D
E
L
M
F
A
B
C
D
E
L
M
F
I-pipe system for space protection