JA-111ST-A BUS combined smoke and heat detector

JA-111ST-A BUS combined smoke and heat detector

1 / 3

MLW21101

This device is a component of the 

JABLOTRON JA-100 

alarm 

system. It is used to detect fire hazards in the interior of residential 
or commercial buildings. The detector is powered by the control panel 
BUS (EN 54-7; EN 54-5). When the detector is powered by inserted 
batteries (3x 1.5 V AA) and it loses BUS power or stops communicating 
with its control panel, it can continue operating as a stand-alone 
detector when the 12 V BUS power supply is disconnected 
(EN 14604). Batteries are not included and we recommend buying them 
with the detector.

The detector indicates a fire risk using the built-in LED indicator and 

acoustic signalling. The detector can also indicate any other type 
of alarm in the system such as intrusion or tampering.

The JA-111ST consists of two independent detectors – an optical 

smoke detector and a heat detector. The optical smoke detector works 
on the principle of scattered light. It is very sensitive to large dust 
particles which are present in dense smoke. It is less sensitive 
to smaller particles generated by the combustion of liquids such 
as alcohol. That is why the fire detector also contains a built-in heat detector 
which has a slower reaction but is much better at detecting fire which 
generates only a small amount of smoke. The detector works in status 
mode so it signals both activation and deactivation. The product is not 
designed to be installed in industrial premises. The product should 
be installed by a trained technician with a valid certificate issued 
by an authorised Jablotron distributor.

Detector placement

The smoke detector must be installed so that any smoke easily drifts 

into the detector owing to natural thermal currents, e.g. on the ceiling.
The detector can only be used in an enclosed interior. It is not suitable 
for places where smoke can be dispersed or it can get cold (interiors 
with extremely high ceilings above 5 m) - the smoke would not reach the 
detector position.

The detector must always be placed in the section leading to the exit 

of the building (escape route), see

Fig. 1

. If the building has a floor area 

greater than 150 m

2

, installation of an additional detector in some other 

suitable place is required, see 

Fig.2

.

1. kitchen, 

2. living room, 

3. – 6. bedrooms

y

/

basic coverage

{

recommended coverage

Fig 1

Fig 2

1

2

3

6

Fig 3

In multi-storey flats and family houses the detector should be installed 

above the stairs. It is recommended to place additional detectors 
in rooms where people sleep. See 

Fig 3

.

Installation on level ceilings

Place the detector in the centre of the room if possible.

The detector must not be recessed into the ceiling due to the possible 
existence of a cool air layer on the ceiling. Never place the detector 
in the corner of the room (always keep at least 0.5 m distance from 

the corner - see Fig 4).

There is an insufficient circulation of air 

in the corners.

Installation on sloping ceilings

If the ceiling is not suitable for mounting on a level surface 

(e.g. a room under a roof ridge), the detector can be installed as in Fig. 5.

Fig 4

0,9 m

Fig 5

centre of the room, best location

acceptable location

Walls, partitions, barriers and lattice ceilings

The JA-111ST-A detector must not be installed closer than 0,5 m

from any wall or partition.

A narrow room with a width of less than 1,2 m

requires the detector(s) to be placed at a distance of at least one third of the 
room’s width away. In a case when a room is separated into sections with 
walls, semi partition walls or furniture which do not reach the ceiling, 
then each section must be consider as fully separated room if the gap 
between the top of these and the ceiling does not exceed 0.3 m.
A free space of at least 0.5 m is required under and around the detector. 
Any irregularities of the ceiling (e.g. girders) exceeding 5 % of the ceiling height 
should be considered a wall and the above mentioned limitations should apply.

Ventilation and air circulation

The detectors must not be installed directly near ventilation or air 

conditioning vents.

In the case of air being supplied through 

a perforated ceiling, each detector must be placed so that no perforation 
hole occurs within 0.6 m of the detector.

Avoid installing the detector in the following places:

places with poor air circulation (niches, corners, apexes 
of A-shaped roofs, etc.)

places exposed to dust, cigarette smoke or steam

places with over-intense air circulation (close to ventilators, heat 
sources, air conditioning outlets, etc.)

in kitchens and other cooking places (because steam, smoke or oily 
fumes can cause false alarms or reduce detector sensitivity).

in areas with lots of small insects which can cause false alarms

Warning:

Most false alarms are caused by improper detector 

placement.

See CEN/TS 54-14 standards for detailed installation guidelines.

Installation

When installing the detector, abide by the procedures recommended 

in the previous paragraphs.

Fig 6: 1 – detector cover opening; 2 – detector cover closing; 

3 – optical status signalling; 4 – arrow showing where to insert the detector; 

5 – bus terminal; 6 – production code; 7 – battery holders

1.

Open the detector cover

, by turning it anti-clockwise 

(1)

2.

Push the BUS cable through the base and attach the base

to the selected place using screws.

3.

Connect the BUS cable.

4.

When the device is switched on, the yellow LED on the PCB 
inside the detector starts flashing repeatedly to indicate that 
the detector has not been enrolled into the system.

When connecting the detector to the 
system digital bus, always switch the 
power off.

5. Proceed according to the control panel installation manual. 

a. Go to the 

F-Link

software, select the required position 

in the 

Devices 

window and launch enrollment mode by clicking 

on the Enroll option. 