JA-111ST-A BUS combined smoke and heat detector

JA-111ST-A BUS combined smoke and heat detector

2 / 3

MLW21101

b. Click to the option “Scan/add new BUS devices” and select this 

detector from the offered list and double-click to confirm 
selection. The yellow LED indicator goes off. 

6. Insert the detector into the plastic base. The detector can be 

inserted in the base in one position only. It is marked with arrows (4) 
on both parts of the plastic housing. When inserting the detector, 
bear in mind that the connecting wires must not restrain 
the functioning of the test buttons.

7. Pre-set the detector functions according to the chapter 

Detector 

settings.

Notes:

We recommend peeling off the sticker with the production code 
(6) before you put it onto the mounting base, stick it on a piece 
of paper and write down the device location for better 
identification of a specific device when enrolling by F-Link 
software.

The detector can also be enrolled by inserting into the mounting 
base and locking by turning it clockwise when enrollment mode 
is open.

The detector can also be enrolled into the system by entering 
its production code (6) in the F-Link software (or using a bar 
code scanner). All numbers stated under the bar code should
be entered (1400-00-0000-0001).

The detector can be operated without batteries. When there are 
no batteries in it, it doesn´t comply with the EN14604 norm. 
Before you insert the detector into the mounting base remove 
the red blocking tabs from the detector body. The mounting base 
must be replaced only by the same bases meant for detector
which is tested by pressing its body (which then works as testing 
switch).

If the yellow LED lights permanently, the detector cannot 
be enrolled and it indicates a fault with the cabling. We strictly 
recommend checking the BUS cables.

Detector setting

The detector properties can be set in the Devices window in

the

F-Link

software (default settings marked by the symbol *):

The 

Reaction

option in the 

Devices 

window allows you to set 

the type of system reaction to the activation of the enrolled detector.

To set the detector properties use the 

internal settings

button. 

This opens a window where you can set internal settings and 
behaviours of the detector.

Reaction:

enables the setting whether the detector should react 

on smoke only, temperature only, smoke or temperature, smoke and 
temperature at the same time; see the following table for details:

Smoke

EN 14604, EN 54-7

Temperature

EN 54-5

*Smoke or temperature

EN 14604, EN 54-5, EN 54-7

Smoke and temperature at once

Thermal class EN54-5 

determines the reaction speed of the detector 

to temperature increases.

*A1 – A fast reaction

to temperature changes. It has to react within 1 

min 40 sec when the temperature reaches 30 °C/s. 

A2 – A slow reaction

to temperature changes. It has to react within 2 

min 25 sec when the temperature reaches 30 °C/s. These detector 
settings have a high immunity to false alarms in problematical 
installations.

Fire alarm acoustic indication:

Source of acoustic indication:

Pre-sets the source of the acoustic 

indication of a fire alarm signalled by the detector (Switched off, *Own 
alarm only, Own and system alarms, System only).

Time limitation of acoustic indication:

An option which serves for 

time limitation of acoustic indication of a fire alarm by the detector; 
optional from 1 to 5 minutes or No limit (*4 min).

Fire alarm indication from sections:

Determines from which 

sections fire alarms will be indicated.

Other alarm acoustic indication:

Indicate another type of section alarm:

Selection of the sections for 

which other alarm types and indications will be signalled.

Alarm reaction: 

Determines when the detector indicates according to 

the *IW (Internal warning) or EW (External warning) signal.

Time limitation of acoustic indication: 

No limit, 1, 2, 3,*4, 5 

minutes. When the No limit option is selected, it means the time is taken 
from the system parameters. Caution: the maximum alarm length in the 
system is 20 minutes.

Muting the system sirens by pressing the detector:

This option 

allows choosing how to react if the acoustic indication of an alarm from
the system sirens can be terminated by pressing the detector against 
the base of the detector. Select from the following options: *Switched 
off, during its own alarm, during a system alarm, Switched on.

Batteries: 

Select the type of batteries used (*alkaline, lithium) 

or operating without batteries (the detector doesn´t check the status 
of inserted batteries).

Test:

By clicking on this button of the detector a self-test (auto test) 

is performed. The result is indicated by a green or red dot. Green = test 
OK, red = fault – in this case repeat the test and if you get the same 
result then the detector should be sent to the service centre.

Fire alarm

Optical detector:

When smoke gets into the detecting chamber, 

an alarm is triggered and indicated optically by a flashing red LED 
(approx. 8x per sec.) and if enabled then also by an acoustic signal 
according to the detector settings. Indication takes place until the space 
around it or the detecting chamber is ventilated. 

Temperature detector:

When the temperature increases above 

a defined limit an alarm is triggered and indicated optically by a flashing 
red LED (approx. 8x per sec.) and if enabled then also by an acoustic
signal according to the detector settings. Indication takes place until 
the temperature is decreased by ventilation, for instance.

Silencing the siren during an alarm:

The siren can be silenced 

by pressing the detector body against the base. The siren is inactive 
for 10 minutes. If the detector still detects smoke or heat after this time, 
the siren is activated again. When the need arises (e.g. in the case 
of a detector failure), it is possible to postpone siren reactivation 
by 12 hours. This can be done by pressing the detector again for 5 s
after silencing the siren. When the detector chirps, you have to release 
the pressure within 1 s. The switchover to the postponed siren mode 
is confirmed with 5 chirps. The detector LED flashes all the time during
the postponement.

Alarm memory: 

When enabled, LED indication continues flashing 

slowly (approx. 2x per sec) for 24 hours after alarm expiration. 
Indication is terminated by performing unsetting procedure on already
unset section where the alarm was triggered. 

Alarm memory in stand-alone mode 

indication can be terminated 

by pressing the detector body against the wall.

Tamper alarm:

When the detector cover is opened, the detector 

sends a tamper signal to the control panel. To avoid tamper alarm 
triggering enter service mode before opening the detector.

Note:

-

When the detector works in stand-alone mode, an alarm is 
indicated acoustically and optically with no option to change it.

Other alarms

The detector can indicate other alarms not just alarms triggered by the 
detector itself. This includes alarms such as intrusion, tampers, panic, 
24 hr and also in relation to IW and EW signals. Settings allow you to 
choose specific sections and limits of the alarm length.

Notes:

The indication of other alarms is influenced by system parameters 
(i.e. Siren when partially set, Siren IW when tamper triggered,…).

Its own alarm always has a higher priority. When its own alarm 
is already being indicated then other alarms are not indicated at all.

A fire alarm has the highest priority. When a tamper alarm, for 
instance, is triggered and suddenly a fire alarm is triggered then 
indication of tampering is cancelled and it starts with fire alarm 
indication immediately.

Detector testing and maintenance

The detector should be tested at least once per month.

To test the 

detector press the detectors body against the base and wait until a LED 
indicator switches on. The LED flashing signals switchover to the testing 
mode. The LED flashes for the whole duration of the test. When the test 
is complete, the LED switches off. The detector then signals the result. 
If the detector beeps once, the test has been done successfully. 
If a failure is discovered, the LED flashes and beeps three times. 
I

n this case repeat the test and if you get the same result then 

the detector should be sent to the service centre.

If the battery is low, 

there is no acoustic signalling but just one flash when the test 
is completed. 

The complete functioning of the optical part of the detector can 

be tested with a testing spray (e.g. SD-TESTER). The heat sensor can 
be tested with heated air (e.g. with a hair dryer). If the control panel 
is not in the SERVICE mode, a fire alarm is triggered.

Warning: never test the detector with fire.

Fault indication

The detector checks its functioning. If it discovers a fault, it chirps and 

flashes the LED three times and then flashes briefly three times every 
30 s (a fault is signalled the same way when an auto-test is performed, 
see the 

Installation

chapter). It could be a faulty detection chamber, an 

environmental temperature out of the working range (see 

Technical 

specifications

) or some other fault detected in the detector. 