Aspirating Smoke Detector
Planning | en
57
Bosch Sicherheitssysteme GmbH
Operation Guide
2018.04 | 2.0 | F.01U.130.926
M-pipe system - simplified planning
1 pipe system
FCS-320-TP1
FCS-320-TT1
2 pipe systems
FCS-320-TP2
FCS-320-TT2
d
d
A
B
C
D
A
B
C
D
FAS / FCS
FAS / FCS
M-pipe system, e.g. for space protection
Limiting values
Min. distance FCS-320 – last T-fitting
2
m
Double U-pipe
Max. distance FCS-320 – last T-fitting
20
m
Max. branch length
20
m
Max. overall pipe length (Ø 25
mm)
80
m
Min. distance between air sampling openings (d)
0.1
m
Max. distance between air sampling openings (d)
4
m
Max. number of air sampling openings (n) per pipe system
18
M-pipe
Number of air sampling openings
3
6
9
12
15
18
Ø of all air sampling openings in mm
a
5.0
3.6
3.0
3.0
2.5
2.5
a
Punch diameter of the aspiration reducing film sheet