en | Planning
Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926
Operation Guide
Bosch Sicherheitssysteme GmbH
I-pipe system
Air sampling
opening
Number of air sampling openings
2
3
4
5
6
7
8
9
10
∅
air sampling
opening in mm
a
A
6.0
5.0
4.2
3.8
3.2
3.0
2.5
2.5
2.0
B
6.8
5.2
4.4
3.8
3.2
3.0
2.5
2.5
2.0
C
-
5.2
4.6
4.0
3.6
3.0
3.0
2.5
2.5
D
-
-
4.6
4.0
3.6
3.4
3.0
3.0
2.5
E
-
-
-
4.4
4.0
3.4
3.4
3.0
3.0
F
-
-
-
-
4.0
3.8
3.4
3.4
3.0
G
-
-
-
-
-
3.8
3.8
3.4
3.4
H
-
-
-
-
-
-
3.8
3.8
3.4
I
-
-
-
-
-
-
-
3.8
3.6
J
-
-
-
-
-
-
-
-
3.6
a
Punch diameter of the aspiration reducing film sheet
I-pipe system activation thresholds
Activation
thresholds
Number of openings
2
3
4
5
6
7
8
9
10
1 obstructed opening
III
III
II
I
I
—
—
—
—
2 obstructed openings
0
0
III
III
II
I
I
—
—
3 obstructed openings
0
0
0
0
III
III
II
I
I
4 obstructed openings
0
0
0
0
0
0
III
II
I
5 obstructed openings
0
0
0
0
0
0
0
0
II
… will be recognized by the setting level x
— not possible, 0 not practical
Example
If 3 of a total of 7 air sampling openings are found to be obstructed, the switch for setting the
airflow monitoring should be set to level III.
Notice!
When planning in accordance with EN 54‑20 or ISO 7240-20, level I or II must always be set
for airflow monitoring.