en | Installing the Aspirating Smoke Detector
Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926
Operation Guide
Bosch Sicherheitssysteme GmbH
1.
Punch out the cable entries using a sharp object.
Caution: Do not cut the cable entries with a knife!
–
Route the connection cable(s) (max. 2.5
mm2) through the prepared M20 or M25
connections and into the unit. Now cut these to the required length inside the unit.
–
Wire the unit according to the connection information described below.
Terminal Terminal block X6 Function
1
Al 1
NO contact for 1st alarm relay
2
C contact for 1st alarm relay
3
NC contact for 1st alarm relay
4
+ Ext. Displ.1
Remote indicator for 1st detector module
5
- Ext. Displ.1
6
+ Reset
+24
V reset input
7
- Reset
0
V reset input
8
+ 24
V
+24
V power supply
9
- 24
V
0
V power supply
Terminal Terminal block X7
1
Fault 2
Fault contact for 2nd detector module
2
3
Al 2
NO contact for 2nd alarm relay
4
C contact for 2nd alarm relay
5
NC contact for 2nd alarm relay
6
+ Ext. Displ.2
Remote indicator for 2nd detector module
7
- Ext. Displ.2
8
Fault 1
Fault contact for 1st detector module
9
Notice!
On Bosch fire panels, use R
A
820 Ohm for the alarm resistor and RE 2k2 (3k9) for the terminal
resistor.