7.5.6
Error Messages
The copy function archives all parameters, regardless of the
access control and the value range. Some of the parameters
are only writable if the frequency inverter is not in operation.
The controller enable input (S1IND/STOA, S7IND/STOB) may
not be activated during the copy operation, otherwise the data
transmission is aborted. The message StO and the number of
the last parameter which was copied are displayed. If the con-
troller enable input is deactivated again, the aborted copy op-
eration is continued.
The data transmission from the selected source to the destina-
tion is continuously monitored by the copy function. If an error
occurs, the copy operation is aborted and the message Err
and an error code are displayed.
Error Messages
Code
Meaning
0
1 Write error in memory of control unit;
repeat the copy operation. If error message is displayed again, format
the memory.
2 Read error in memory of control unit;
repeat the copy operation. If error message is displayed again, format
the memory.
3 The size of the memory of the control unit was not determined correct-
ly.
If this error occurs repeatedly, replace the control unit.
4 Not enough memory; the data are incomplete.
Delete the incomplete file and date no longer needed from the control
unit.
5 The communication has been disturbed or interrupted;
repeat the copy function, delete the incomplete file if necessary.
1
0 Invalid identification of a file in the operating unit;
delete faulty file and format memory if necessary.
2 The memory space of the selected target file is occupied;
delete file or use different target file in the operating unit.
3 The source file to be read in the control unit is empty;
only files containing reasonable data should be selected as a source.
4 Defective file in the control unit;
delete defective file and format memory if necessary.
2
0 The memory in the control unit is not formatted;
format the memory via the FOr function in the copy menu.
3
0 Error during reading of a parameter from the frequency inverter;
check connection between the control unit and the frequency inverter
and repeat reading operation.
1 Error during writing of a parameter in the frequency inverter;
Check connection between the control unit and the frequency inverter
and repeat the writing operation.
2 Unknown parameter type;
delete faulty file and format memory if necessary.
4
0 The communication has been disturbed or interrupted;
repeat the copy function, delete the incomplete file if necessary.