Actual Values of the Frequency Inverter
269 Warnings
Warning message with error code and abbreviation.
273 Application Warnings
Application Warning message with error code and
abbreviation.
275 Controller Status
The reference value signal is limited by the controller
coded in the controller status.
277 STO Status
Signal state of the shutdown paths STOA (digital input
S1IND/STOA) and STOB (S7IND/STOB) of the safety
function “STO – Safe Torque Off”.
278 Frequency MFO1F
Output signal on multifunctional input 1 in
Operation
mode
550 – repetition frequency.
Additional to the described Actual values further Actual values are available for Fieldbus
access. These are notable parameters
Current error
260
,
Warnings
270 and
Applica-
tion Warnings
274
,
in which the respective feedback can be readout as a hexadecimal
code (and without text). Please refer to the Communication manuals.
The actual values can be read out and monitored in the VAL menu branch of the oper-
ating unit. The parameter
Operation level
28 in the PARA menu branch defines the
selection of the actual value parameters.
The digital inputs may seem deactivated in the actual value display 243, 250 (con-
stant “0”). This can be caused by the used configuration or used functions (in example
encoder or frequency input).
Input
Deactivation mechanism for Actual value display
S2IND
PWM / Rep. freq. input
S4IND
Track B (Encoder 1)
S5IND
Track A (Encoder 1)
S6IND
Track Z (Encoder 1) or
PWM / Rep. freq. input
MFI1
Analog input
Settings:
For Encoder 1, check Parameter
Operation mode
490.
For PWM / Rep. Freq. input, check Parameter
Operation mode
496.
For MFI1 check Parameter
Operation mode
452.
Actual value:
Encoder 1: Frequency is displayed in 217, speed in 218.
PWM / Rep. freq. input: PWM is displayed in 258, frequency in 252.
258
Operating Instructions ACU
06/13