Control / Reference Value
The device control commands are triggered by the following bit combinations in the Control Word:
Control Word
Command
Bit 7
Bit 3
Bit 2
Bit 1
Bit 0
Transitions
Reset Fault
Enable
Operation
Quick Stop
Enable
Voltage
Switch On
Shutdown
X
X
1
1
0
2, 6, 8
Switch On
X
0
1
1
1
3
Switch On
X
1
1
1
1
3
Disable Voltage
X
X
X
0
X
7, 9, 10, 12
Quick Stop
X
X
0
1
X
7, 10, 11
Disable Operation
X
0
1
1
1
5
Enable Operation
X
1
1
1
1
4
Reset Fault
0
1
x
x
x
x
15
"X" means any value.
Transition 3 (Command "Switch On") is only processed if Bit 4 "Voltage enabled" in the Status Word is
set.
The status word reflects the operation state.
Status Word
State
Bit 6
Bit 5
Bit 3
Bit 2
Bit 1
Bit 0
Switch On
disabled
Quick Stop
Error
Operation
enabled
Switched
On
Ready to
Switch On
Switch On disabled
1
X
0
0
0
0
Ready to Switch On
0
1
0
0
0
1
Switched On
0
1
0
0
1
1
Operation enabled
0
1
0
1
1
1
Quick Stop active
0
0
0
1
1
1
Error Reaction active
0
X
1
1
1
1
Error
0
X
1
0
0
0
"X" means any value.
Bit 7 "Warning" can be set at any time. It signals a device-internal warning. The active warning can
be read out from the Warning Status with Parameter
Warnings
270.
Bit 9 "Remote" is set if the operation mode "Control via Statemachine" (
Local/Remote
412 = 1) is
set, and the Controller Release is switched on.
Logical combination of the digital control signals:
STO = (STOA and STOB) AND (Start Right OR Start Left).
The frequency inverter can only be controlled, if the logical combination is true. The logical inputs for
Start Right and Start Left can be directly linked to "On" or "Off" (Parameter
Start Clockwise
68 and
Star Anticlockwise
69).
Bit 10 "Reference frequency reached" is set when the specified reference value is reached. In the
special case of power failure regulation, the bit is also set when the power failure regulation reaches
the frequency 0 Hz (see frequency inverter operating instructions). For "Reference value reached"
there is a hysteresis (tolerance range) which can be set via Parameter
Reference Value Reached:
Hysteresis
549 (see frequency inverter operating instructions).
Bit 11 "Limit value reached" indicates that an internal limit is active. This may be the current limit,
the torque limit or the overvoltage control. All functions result in the reference value being left or not
reached.
Summary of Contents for Agile
Page 1: ...Agile Modbus Communication manual Frequency inverter 230V 400V ...
Page 2: ......
Page 5: ...Modbus Agile 5 02 2011 13 2 Warning Messages Application 76 13 3 Error Messages 76 INDEX 77 ...
Page 44: ...Modbus Agile 02 2011 44 Handling of Data Sets Cyclic Writing ...
Page 69: ...Modbus Agile 69 02 2011 10 2 1 Statemachine diagram ...
Page 78: ......
Page 79: ......