Modbus Agile
02/2011
62
Control / Reference Value
10 Control / Reference Value
410 Control Word
411 Status Word
484 Reference Frequency RAM [Hz]
524 Reference Percentage RAM [%]
The frequency inverter can be controlled completely via the serial interface. The following parameters
and actual values are used for this:
Parameter
Setting
No. Name/Meaning
Min.
Max.
Factory Setting
Type
410 Control Word
0x0000
0xFFFF
-
uInt
411 Status Word
0x0000
0xFFFF
-
uInt
484 Ref. Frequency Value RAM [Hz]
-999,99
999,99
0,00
Long
524 Ref. Percentage RAM [%]
-300,00
300,00
0,00
Long
With the
Control Word
410 (data type uInt), control commands are sent to the frequency inverter.
With the
Reference Frequency RAM
484 (data type Long [Hz]) or
Reference Percentage RAM
524
(data type Long [%]), the reference line value is sent. Via the
Status Word
411 (data type uInt), the
status of the frequency inverter is read out.
M
Master
(z.B. PC)
Inverter
Release
external Release
SPS
Sollwert
Controller Release
&
Frequency Inverter
Control Word,
Frequency Ref. Value
Procentage Ref. Value
Status Word,
Actual Frequency
Actual Speed
Cm
232
/
Cm
48
5/
Ser
vi
ce
In
ter
fa
ce
RS
232/
RS
48
5
Note:
Control Word
410,
Reference Frequency RAM
484 and
Reference Percentage RAM
524 are stored
in the RAM of the frequency inverter. This is generally addressed via data set 0.
Summary of Contents for Agile
Page 1: ...Agile Modbus Communication manual Frequency inverter 230V 400V ...
Page 2: ......
Page 5: ...Modbus Agile 5 02 2011 13 2 Warning Messages Application 76 13 3 Error Messages 76 INDEX 77 ...
Page 44: ...Modbus Agile 02 2011 44 Handling of Data Sets Cyclic Writing ...
Page 69: ...Modbus Agile 69 02 2011 10 2 1 Statemachine diagram ...
Page 78: ......
Page 79: ......