Control / Reference Value
Status Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0
Ready to Switch On
1
Switched On
2
Operation enabled
3
Error
4
Voltage enabled
5
Quick Stop
6
Switch On disabled
7
Warning
8
no function
9
Remote
10
Reference value reached
11
Limit value reached
12
no function
13
no function
14
no function
15
Manufacturer dependent
Warning 2
Bit 4 "Voltage enabled" in the Status Word indicates the current status of the mains supply.
Bit 4 "Voltage enabled" = 0 signals "no mains supply" and that starting the drive is not possible.
Bit 4 "Voltage enabled" = 1 signals "mains supply switched on" and drive ready for starting.
Note:
The frequency inverter supports an external 24 V voltage supply for the control electronics of the fre-
quency inverter. Communication between the controlling device (PLC) and the frequency inverter is
still possible even when the mains supply has been switched off.