INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Pellet burner Bisolid GP xx R tsc OM-BSGPRTSCV00/11/2016/EN
16
5. OPERATION AND CONTROL OF PELLET BURNER SERIES
BISOLID GP XX R TSC
5.1. DESIGNATION OF THE PELLET BURNER CONTROLLER
The controller is designated to provide automatic control of the combustion process and
adjustment of the tube pellet burner’s heating output with two augers, depending on the
building and premises heating needs.
5.2. OPERATION OF THE PELLET BURNER CONTROLLER
The device can control the following system modules:
Fuel transport auger 1.
Fuel transport auger 2.
Fresh air and extraction fans.
Electrical heating element for ignition of the pellets.
Cleaner element for ash cleaning.
Circulations pump for the boiler.
At primary switch on, as well as when switching the power supply off, the burner
goes through stop procedure.
5.3. STARTING THE PELLET BURNER
When missing stop signal or in case of emergency situation and there is difference between
the adjusted and the measured temperature from the To sensor, then the burner starting
procedure initiates. The initial fuel doze is loaded and the ignition switches on. After
establishing the presence of flame the burner heating output increases. When the modulation
zone „Zone_reg” has been reached the burner heating output decreases and when the
desired temperature has been reached the burner operates at its minimum heating ouput.
When higher than the adjusted temperature has been reached, the system responds with stop
procedure.
5.4. SWITCHING OFF THE PELLET BURNER
Т
,
Т
_set
T
P,%
P
ma
zone_reg
Т
_set - zone_reg
P
mi