INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Pellet burner Bisolid GP xx R tsc OM-BSGPRTSCV00/11/2016/EN
18
When there are switches on and off from the room regulator and it operates without
optimization (0), the heating water adjustment becomes:
At start - maximum.
At stop – minimum.
When there are switches on and off from the room regulator and it operates with optimisation
(5-60 min.), the heating water adjustment becomes:
At start – increase starts, as the maximum assigned temperature value is reached at
the end of the optimization time, only in case there is no stop occured during this
period.
At stop – decrease starts, as the minimum assigned temperature value is reached at
the end of the optimization time, only in case there is no start occurred during this
period.
5.8. TEMPERATURE AND SECURITY RESTRICTIONS
When managing the rotary tube pellet burner series Bisolid GP xx R tsc it is necessary to
consider the following temperature and security limitations:
Minimum assignemt for inlet water temperature.
Maximum assignemt for inlet water temperature.
Water freezing protection.
Boiler overheating and „back-fire” protection.
Circulations pump blocking protection.
The minimum and the maximum assignment of the heating water temperature determinate the
limits of the supplied water to the premises. (See section "Service Settings").
Water freezing protection – starts the burner when the temperature is below 5
°
С
. Boiler overheating and „back-fire” protection – input signal from the blocking
thermostat, and when the signal contact is opened the burner stops.
Circulations pump blocking protection – drives/rotates the pump for 5 minutes,
in case it has not been operating for at least 24 hours.
5.9. FRONT CONTROL PANEL OF THE PELLET BURNER
The front control panel is presented in Figure 7 – intuitive LCD display of rotary tube pellet
burner series Bisolid GP xx R tsc. The indication of the pellet burner parameters is given in
Figure 8.