FDL (E2) 03/2011
page 44/68
Normal Display
Display 1 shows
e.g. 19.8
(actual temperature value)
Display 2 shows e.g. 15.05.06 13:52 - -
(actual date and time, actual switching state of week pro-
gram timer channel 1: Off, channel 2: Off)
Press down key
for 5 sec
Display 1 shows
e.g. 0000
Display 2 shows
PROGRAM EDITOR
(you are in the program editor)
Press down key
for 5 sec
Display 1 shows
0000
Menu visible only if week program timer is activated.
Display 2 shows WEEK PROG. EDITOR
(you are in the week program editor)
Press down key
for 5 sec
Display 1 shows
0000
Display 2 shows
USER – LEVEL
(you are in the user level)
Press program key
Display 1 shows
0000
Display 2 shows UserCod?
0000
(enter user code, display flashes)
Enter the user code using arrow keys
e.g.
0001
(basic setting,
or the valid code in case it has been previously
changed in this menu).
Value is shown in both displays.
Automatically forward after 2 sec
Display 1 shows
1
(actual address: 1)
Display 2 shows Adress
1
(entry of unit address)
(actual address: 1)
Enter the unit address (1 up to 254) using
arrow keys
Address is shown in both displays.
Press key
Display 1 shows
1
(actually valid user code: 1)
Display 2 shows User-cod
1
(change user code)
(actually set: 1)
Enter a new value using arrow keys
Value is shown in both displays.
Press key
Display 1 shows
0000
(no function)
Display 2 shows Saf.mode: Limit
(no function)
Press key
Display 1 shows
0
(no function)
Display 2 shows Saf.setp
0
(no function)
Press key
Display 1 shows
0000
(no function)
Display 2 shows Decimal:
XXX.X
(setting of decimal point position)
(actual setting: XXX.X)
Select decimal point position using arrow
keys
Decimal point position XXX.X or XXXX. is
shown in display 2.
Summary of Contents for 9010-0269