Next step – set-point entry in the desired program sections:
Basic entry principle:
Access the parameters of individual program sections with button X/W one after
the other. Enter the values of the individual parameters with the arrow keys. A value flashing once after 2
seconds indicates that it has been adopted by the controller. If several parameters are to be skipped (e.g.
in order to change a parameter in a posterior program section), the parameters can be rapidly jumped
over by holding down the X/W key. If no button is pressed for more than 120 sec the controller switches
back to Normal Display. The program entered to this point remains stored.
Press key
Display 1 shows
e.g. 40.0
C
(actual temperature set-point)
S01: TEMP 40.0
(variable: temperature in °C)
Display 2 shows
alternating
CONTINUE X/W
(information: go on with X/W)
Enter temperature set-point of S01 in °C
using arrow keys
Press key
Display 1 shows
e.g. 00.30
(actual section length set-point)
S01: TIME 00:30
(variable: section length in hh:mm)
Display 2 shows
alternating
CONTINUE X/W
(information: go on with X/W)
Enter section length set-point of S01 in
hh.mm using arrow keys
Value is shown in both displays.
Press key
Selecting the next program sections to be entered
Display 1 shows
e.g. 02
(section S02 selected)
P01: --- SEC.
Display 2 shows
alternating
CONTINUE X/W
Section S02 has already been created.
enter new set-points for the individual parameters with X/W.
or:
Display 1 shows
e.g. 02
(section S02 selected)
P01: --- SEC.
Display 2 shows
alternating
NEW SEC. X/W
Section S02 has not yet been created.
enter set-points for the individual parameters with X/W
Select the next section to be entered using
arrow keys
Display 1 shows
e.g. 60.0
C
(actual temperature set-point)
S02:TEMP 60.0
(variable: temperature in °C)
Display 2 shows
alternating
CONTINUE X/W
(information: go on with X/W)
Enter the temperature set-point of S02 in °C
using arrow keys
Etc.
If all sections up to S10 or up to S20 have been programmed, section S01 follows again. In order to quit
the entry mode, press the “
EXIT
” button several times or wait 120 sec
→
the controller will then return to
Normal Display.
When changing the set-point, check the setting of the safety device (chap. 12.1).