FDL (E2) 03/2011
page 22/68
CAUTION
Danger by stacking.
Damage to the units.
∅
Do NOT place safety / paint drying ovens on top of each other.
To completely separate the unit from the power supply, you must disconnect the power plug. Install the
unit in a way that the power plug is easily accessible and can be easily pulled in case of danger.
Do not install or operate the oven in potentially explosive areas.
DANGER
Explosion hazard.
Danger of death.
∅
Do NOT operate the unit in potentially explosive areas.
∅
KEEP explosive dust or air-solvent mixtures AWAY from the vicinity of the unit.
The standard equipped safety / paint drying oven FDL with housing protection IP 33 acc. to DIN 40050
(see type plate) must NOT be installed and operated in explosive and fire-endangered areas.
If the safety / paint drying oven is optionally built up with housing protection IP 54, it can be operated in
fire-endangered areas. Decisive is always the indication on the type plate.
When operating the safety / paint drying oven FDL with housing protection IP 54 in fire-
endangered areas, observe DIN VDE 0100-482:2003 (for Germany).
Operation of the cooling slots must on no account be impaired. The vapors produced when the heating
the content must be extracted from the safety / paint drying oven through non-combustible exhaust gas or
exhaust air ducts. The exhaust duct (nominal diameter 100 mm /
3.9 in
) on the rear of the chamber
serves for this purpose, to which a suitable exhaust air duct can be connected, e.g., a corrugated alumi-
num hose. The exhaust connection must be made via a draught limiter; the exhaust air must not be
guided into ducts for combustible gas.
CAUTION
The rear exhaust duct will become hot during operation.
Danger of burning.
∅
Do NOT touch the exhaust duct during operation.
4.
Installation of the equipment
4.1
Operating instructions
Depending on the application and location of the unit, the operator of the safety / paint drying oven must
provide the relevant information for safe operation of the unit in a set of operating instructions.
Keep these operating instructions with the unit at all times in a place where they are clearly
visible. They must be comprehensible and written in the language of the employees.